WHY IS MAKE-UP AIR IMPORTANT?
If you have ever dined in a space with an overwhelming aroma from the kitchen or opened the door to a restaurant and felt a rush of outdoor air enter the building, you have experienced a kitchen with an imbalanced ventilation system. Cooking applications create an abundance of smoke, grease and odor and the purpose of commercial hood systems is to continuously exhaust a significant amount of this contaminated air. Once the contaminated air is pushed to the outside, fresh air, commonly referred to as “make-up air,” is needed to exchange the exhausted air. Each kitchen’s make-up air process may be handled with a different solution or style of unit(s) – though each shares the goal of replacing the air removed by the exhaust fan and maintaining proper balance by bringing fresh outdoor air back into the kitchen.
Selecting the correct make-up air solution for your kitchen can be the key to providing your customers and staff with an excellent experience. Here are a few options to consider when designing for your space.
When is Make-up Air Required for Kitchens?
Most building codes require make-up air in any commercial kitchen operation to combat negative pressure and provide a safe and comfortable environment for all. Section 508.1 of the International Mechanical Code (IMC) states:
“Make-up air shall be supplied during the operation of commercial kitchen exhaust systems that are provided for commercial cooking appliances.”
While the Uniform Mechanical Code (UMC) states in section 511.3:
“The make-up air quantity shall prevent negative pressures in the commercial cooking area(s) from exceeding 0.02-inch water column”
And standard 96 of the National Fire Protection Association (NFPA 96) states in section 8.3.1:
“Replacement air quantity shall be adequate to prevent negative pressures in the commercial cooking area(s) from exceeding 4.9 Pa (0.02 in. water column).”
Make-up air is even required in certain residential kitchens, like those that may be needed in assisted living care centers, fire stations, or daycare facilities. Section 505 of IMC states:
“Exhaust hood systems capable of exhausting in excess of 400 cfm shall be provided with make-up air at a rate approximately equal to the exhaust air rate.”
Aside from the code requirements, make-up air also plays a pivotal role in the function of an exhaust system. In the absence of a make-up air solution, the exhaust fan’s continuous removal of air from the space creates negative pressure in the building. One easily apparent example of negative pressure is when it becomes more difficult to open doors in a restaurant or other commercial kitchen space. This negative pressure can significantly diminish the performance of the exhaust fan – resulting in a drop of the contaminated air being exhausted by up to 30%. With this pressure imbalance leading to reduced effluent capture by the hood, it may seep into the seating area and consequently make for unhappy customers.
TYPICAL Make-up Air Applications
Figure 1: Traditional Restaurant Design
This setup is commonly seen in commercial kitchens – typically those with a traditional restaurant design with specific front-of-house (dining) and back-of-house (kitchen) operations.
Advantages of the traditional restaurant make-up air design:
Figure 2: Restaurant Design with DOAS
This setup is becoming more common in certain applications – typically restaurants with a small footprint or open concept design that combines the kitchen and dining areas into a single space.
Advantages of the restaurant design with DOAS:
Make-Up Air Requirements in Other Occupied Spaces
While commercial kitchens require make-up air to replace the hood’s exhausted air, dining and other occupied spaces in the building also need a certain amount of fresh air, the quantity of which is a factor of both the occupancy level and area of the space. Furthermore, current trends have encouraged increased ventilation with fresh air. Traditionally, RTUs have only been responsible for providing lesser amounts of required fresh air to non-kitchen areas, see Figure 3.
Figure 3: Typical Building Setup – RTUs for Marginal Outdoor Air Replacement
This traditional application’s limits become apparent with high occupancy buildings or other spaces which require additional outdoor air. RTUs are limited in the amount of outdoor air they can supply relative to the volume of air they need to recirculate. Such buildings typically require multiple units including additional make-up air systems, resulting in oversupply and oversized ductwork. These applications would be better suited with a DOAS unit, see Figure 4.
Figure 4: High Volume Operation – Building with Multiple MAUs and DOAS
Figure 4 shows multiple systems that can provide both the comfort control of an RTU and the required outdoor air to the space. You can simplify the space by replacing several RTUs with fewer make-up air units and one DOAS, simplifying controls and reducing installation costs.
Figure 5: High Occupancy or Other Building Requiring Significant Outdoor Air – DOAS
Figure 5 illustrates the better option to simplify a space with a high occupancy system by replacing multiple RTUs and make-up air units with a single DOAS unit, streamlining control sequences and reducing installation costs. One DOAS unit provides full temperature and humidity control with fewer roof penetrations and runs of power and reduces footprint on a building’s roof.
Improved Comfort Control with Make-Up Air Units
Past make-up air units were commonly configured with marginal tempering options. In most cases, a kitchen’s make-up air unit was untempered or just included heat. While untempered options are a highly economical solution, their lack of comfort control must be resolved through secondary units, or otherwise risk an uncomfortable and sometimes hazardous environment. With current trends towards reducing employee turnover and providing a better working space, make-up air solutions with greater tempering controls are becoming more common. Comfort control options in typical make-up air units are expanding, including options for direct or indirect gas, hot water, steam, or electric heat, and evaporative, direct expansion, or chilled water cooling.
Heating and cooling setpoints (outdoor temperature at which the heating and cooling functions initiate) are just as critical as the type of tempering provided on a unit. For instance, a unit equipped with cooling is not effective if it does not begin cooling until the outside air reaches 85°F. Therefore, it is equally important that a unit not only has tempering but is also capable and configured to provide that tempering once the outdoor air begins to become uncomfortable. The International Mechanical Code reinforces the necessity for comfort in kitchens, as it states in section 508.1.1:
“The temperature differential between makeup air and the air in the conditioned space shall not exceed 10°F except where the added heating and cooling loads of the makeup air do not exceed the capacity of the HVAC system”
Integration to Kitchen Controls
Just as codes require the presence of make-up air in commercial kitchens, they also dictate how kitchen make-up units are to operate with respect to the rest of the kitchen ventilation system. IMC 508.1 states:
“… Mechanical make-up air systems shall be automatically controlled to start and operate simultaneously with the exhaust system.”
Make-up air units are required to be tied into the kitchen control package, which is connected to the exhaust fan, hood sensors, and fire extinguishing system. This ensures the entire ventilation system operates together and in accordance with code. Furthermore, kitchen control packages configured for variable volume, a system capable of adjusting exhaust fan and make-up air volumes as cooking loads change, are becoming more common with “green” building trends and a greater emphasis on operational cost savings. With codes in many cases requiring these systems to provide airflow volume reductions of 50%, it is essential to ensure both the exhaust and make-up air can modulate their speed to meet those levels. This is critical, especially on the make-up air unit, as certain units are unable to lower their speeds while also maintaining their tempering functionality.
Lastly, make sure to be aware of any local code requirements that may not exist in the national code books. As an example, certain jurisdictions in Minnesota require proving airflow of the exhaust fan before the make-up air can even initialize.
Summary
Make-up air is a critical component of commercial kitchen ventilation systems. Beyond being required by code, make-up air is responsible for balancing the space, providing comfort, and replacing exhausted air. The method of bringing make-up air into the space and the make-up air unit’s functionality is highly configurable to accommodate any kitchen. Make-up air units paired with rooftop units, or standalone DOAS units, are common configurations to ensure a properly ventilated commercial kitchen and dining area, providing increased comfort for staff and guests.
At Accurex, we believe there is a better way to help simplify the most challenging kitchen ventilation system environments, from engineering to aftermarket support. As a Greenheck Group Company, we have more than 70 years of manufacturing and engineering experience in air movement and control products and offer a breadth of configurable products and services tailored to meet your needs.